M&C rewinds compressor motor stator
1 October 2019
Electrical switching & drive systems & components
Marthinusen & Coutts (M&C) recently provided a solution to an irregularity that occurred in the stator of a large 36 MW compressor motor deployed at Sasol’s Secunda plant.The results of final tests, conducted by HV Test Filed Services on the stator after M&C; had completed all the necessary repairs on it, were found to be the best among many such tests conducted on similar equipment over a period of several decades.
Initially a Sasol maintenance team discovered during a routine inspection in January 2018 that the flux shield mountings on the stator were faulty, whereupon Sasol awarded M&C; a contract to identify the cause of the irregularity and offer a remedy.
“We tested the stator winding, which we found to be fine, but confirmed that there was a defect in the flux shield and recommended that it be repaired, as there was a risk of it damaging the winding if left to continue operating in its existing condition. To repair the flux shield meant also having to remove the winding and perform a rewind on the stator,” said Rob Melaia, M&C’s engineering and technical executive.
Sasol accepted M&C’s recommendation and in August last year assigned it to perform the required repairs. “In addition to replacing the old bars with new bars purchased from a reputable coil manufacturer in the US, we did a very specific modification to repair the flux shield to prevent a recurrence of the defect in the future,” Melaia added. “On investigating the defect we found that the electrical current, instead of flowing only in the flux shield as it ought to have done to prevent the core from overheating, had started flowing in the mounting bolts, so causing wear by electrical arcing in the mounting holes and the mounting studs.”
The solution M&C’s repair team provided was to fit copper braid straps from several points on the flux shield to the stator body to reroute the current in such a way as to prevent a repeat of the damage as witnessed. To confirm the effectiveness of the solution M&C; arranged to have the refurbished stator tested by local independent test authority HV Test Field Services.
Partial discharge and Tan Delta tests were conducted, being the recognised tests for determining the integrity and efficiency of medium voltage windings. The results were:
• A maximum partial discharge of below 250 PicoCoulombs (pC) at 120% of phase voltage.
• In the Tan Delta tests the dielectric dissipation factor was found to be 65 x 10-4 at 20% of phase voltage and 105 x 10-4 at 100% of phase voltage.
“These test results were the best ever to be achieved among the numerous machines on which HV Test has conducted tests of this kind!” Melaia concluded. “We have every reason to be proud of this outcome as it says volumes about M&C’s expertise in this field, both in terms of correctly diagnosing and repairing faults in a wide range of large rotating equipment, as well as providing the appropriate and most effective solutions for them,”
Further reading:
Magma X100 delivers AMB systems for wide range of industrial machinery
Electrical switching & drive systems & components
SpinDrive launches Magma X100 controller, bringing active magnetic bearing technology to a new generation of industrial applications. The Magma X100 expands SpinDrive’s oil-free, frictionless AMB technology to applications below 150 kW, unlocking new addressable markets.
Read more...
Mammoet completes major bridge replacement at Amsterdam Centraal Station
Electrical switching & drive systems & components
Mammoet completes the second of five major bridge replacements at Amsterdam Centraal Station, transporting steel deck sections by water to keep the station open throughout the works.
Read more...
Compressorless hydrogen turbine generates electricity using detonation waves
Electrical switching & drive systems & components
Researchers at the Karlsruhe Institute of Technology (KIT) have demonstrated a hydrogen gas turbine that generates electricity without a mechanical compressor.
Read more...
Why lubrication fails in mining and what to do about it
Editor's Choice Electrical switching & drive systems & components
Lubrication Engineers explains the recurring failure points behind mining lubrication problems and how the right product, storage and application practices can improve equipment reliability.
Read more...
Echain protects cables in cleanrooms
igus
Electrical switching & drive systems & components
Advanced polymer manufacturer igus has developed a new cleanroom energy chain with an innovative guide system that allows for abrasion-resistant travel over distances of up to 30 metres.
Read more...
PowerFlex drives cut energy use by up to 30% amid rising costs
Electrical switching & drive systems & components
Rockwell Automation’s PowerFlex 755TS variable frequency drives are delivering energy reductions of 10 to 30% in Africa’s industrial operations, with adaptive control and predictive maintenance features that cut downtime by up to 50%.
Read more...
Next-generation oil-free motor systems with active magnetic bearings
Electrical switching & drive systems & components
WEG and SpinDrive are collaborating to integrate SpinDrive’s AMBs and built-in IoT condition monitoring into WEG’s market-leading electric motor offering, creating an oil-free, maintenance-free drive solution.
Read more...
Direct drive with integrated control
Vepac Electronics
Electrical switching & drive systems & components
The PSD 40 direct drive is a mechatronic system with integrated control, bus interface and absolute measuring system, with no battery required.
Read more...
AI-powered on-premises analytics for industrial drives
Siemens South Africa
Electrical switching & drive systems & components
Siemens is introducing a new on-premises analytics solution for industrial drive systems. The software enables users to evaluate drive data entirely within their own infrastructure and meet stringent data-sovereignty requirements.
Read more...
Hydrostatic machine base for ultra-precision grinding centre
Electrical switching & drive systems & components
Hyprostatik Schönfeld has developed a high-precision hydrostatic machine base for a new ultra-precision grinding centre for Optotech. The machine platform enables a previously unattainable combination of dimensional accuracy, dynamics and surface quality in the ultra-precision grinding of optical surfaces.
Read more...